AEG R+ FD/FE/FG Molded Case Circuit Breaker
3-630 A · 3P/4P · Icu=Ics 150 kA · interchangeable trip
AEG R+ (Record Plus upgrade) molded case circuit breakers protect, isolate and switch low-voltage distribution circuits. Three frame sizes cover 3-630 A with 3/4 poles, fixed, plug-in and withdrawable versions, interchangeable trip units and Icu = Ics up to 150 kA.
Technical parameters
Data from the AEG official product page and AEG full-line catalog. Values vary by frame and version; confirm the exact configuration before ordering.
| Frame sizes | FD160 / FE160 / FE250 / FG400 / FG630 |
| Rated current | 3-160 A (FD), 25-250 A (FE), 250-630 A (FG) |
| Poles | 3 / 4 |
| Rated insulation voltage Ui | 750 V (FD) / 1000 V (FE) |
| Rated impulse withstand Uimp | 8 kV |
| Rated operational voltage | AC 690 V / DC 500 V |
| Icu at AC 400 V | Up to 150 kA (Icu = Ics) |
| Mechanical life | 10,000 / 25,000 / 40,000 operations (by version) |
| Trip units | Interchangeable; thermal-magnetic LTM / LTMD / GTM, magnetic-only, electronic LSI / LSIG |
| Mounting | Fixed / plug-in / withdrawable |
Standards and accessories
| Standards | IEC 60947-2 (utilization category A) |
| Isolation | Suitable for isolation, positive open/close indication |
| Accessories | EM motor operator, RH rotary handle, SHT, UVR, AS, alarm contacts, RCD, plug-in module |
Key features
Rotating double-break design
High breaking capacity up to 150 kA with Icu = Ics and extremely high reliability.
Cascading technology
Leading cascading technology delivers high system selectivity and reliable protection of the distribution network.
Visual fault diagnosis
Dedicated visual window identifies overload or short circuit at a glance; opening the cover in the ON position trips the breaker automatically.