AEG SecoVac VB2 Plus G Generator Circuit Breaker
15 kV · 2500-5000 A · 31.5-50 kA · IEC/IEEE 62271-37-013
AEG/GEIS SecoVac VB2 Plus G is a generator circuit breaker installed between the generator and step-up transformer. It is designed and tested to IEC/IEEE 62271-37-013 for high continuous current, high DC components, delayed current zero and severe transient recovery voltages.
Technical parameters
Data from SecoVac medium-voltage breaker catalog ACNCMVAA24V1 and SecoVac VB2 Plus IEEE brochure GENCMVAF26V1. * 4000/5000 A versions require forced air cooling; confirm exact current and breaking-current combinations before ordering.
| Series | AEG / GEIS SecoVac VB2 Plus G |
| Rated voltage | 15 kV |
| Rated frequency | 50 / 60 Hz |
| Rated current | 2500 / 3150 / 4000* / 5000* A |
| System-source fault breaking current (Isc) | 31.5 / 40 / 50 kA |
| Generator-source fault breaking current (Iscg) | 15.8 / 25 / 25 kA |
| Out-of-step making / breaking current | 15.8 / 20 / 25 kA |
| Short-time withstand current (3 s) | 31.5 / 40 / 50 kA |
| Peak withstand / making current | 86.3 / 110 / 137 kA |
| DC component | 75% system-source; 130% generator-source |
| TRV peak / rate of rise | 27 kV, 3.5 kV/us (system and generator source); 39 kV, 3.3 kV/us (out-of-step) |
| Rated operating sequence | CO-30min-CO |
| Mechanical life | 10,000 operations |
| Opening / closing time | 20-50 ms / 30-70 ms |
| Main-circuit resistance | <= 35 micro-ohm |
| Closing / opening and motor voltage | AC 110/220 V, DC 110/220 V; charging time <= 10 s |
| Construction | Withdrawable (W) or fixed (F); 275 mm pole centres; spring mechanism |
Standards & operating conditions
The VB2 Plus G generator circuit breaker was type-tested at KEMA and meets the IEC/IEEE dual-standard requirements for generator circuit breakers.
| Generator circuit-breaker standard | IEC/IEEE 62271-37-013, tested at KEMA |
| IEC / GB / DL standards | IEC 62271-100:2012; IEC 60694:2002; GB/T 1984-2014; DL/T 403-2000; DIN VDE 0671 |
| IEEE application reference | IEEE C37.04, C37.06, C37.09, C37.20.2 for the 15 kV VB2 Plus family |
| Ambient temperature | Max +40 °C; min -15 °C (standard order); max daily average +35 °C |
| Relative humidity at 25 °C | Daily average <= 95%; monthly average <= 90% |
| Altitude | Standard version up to 1000 m; high-altitude version on request |
| Site conditions | Indoor; no dripping water, fire/explosion hazard, corrosive gas, severe pollution or violent vibration |
IEEE supplement: SecoVac VB2 Plus IEEE brochure (PDF)
Key features
Built for generator circuits
Installed between the generator and step-up transformer, with higher continuous current, breaking current and DC-component capability than general distribution breakers.
Severe fault conditions
Designed for high system-source DC components (75%), delayed current zero under generator-source faults (up to 130% asymmetry) and high TRV/RRRV stresses.
Out-of-step switching
Capable of making and breaking under out-of-phase conditions, with recovery voltage across the open contacts reaching twice the rated phase-to-earth voltage at 90 degrees.
Typical applications
Power plants, mining, standby/backup generation, semiconductor manufacturing and data-centre generator sets, including unit-connected generator-transformer arrangements.