12 / 24 kV · 630-5000 A · 25-50 kA · 30,000 operations
AEG/GEIS SecoVac VB2 Plus is an indoor three-phase AC vacuum circuit breaker for 12 kV and 24 kV distribution systems. It is available in withdrawable or fixed constructions for frequent operation in industrial, power plant and substation applications.
Technical parameters
Data from SecoVac medium-voltage breaker catalog ACNCMVAA24V1 and VB2 Plus IEEE brochure GENCMVAF26V1. * 4000/5000 A versions use forced air cooling; exact current/breaking-current combinations are confirmed in the order form.
| Series | AEG / GEIS SecoVac VB2 Plus |
| Rated voltage | 12 / 24 kV |
| Rated frequency | 50 Hz |
| Rated current at 12 kV | 630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000* / 5000* A |
| Rated current at 24 kV | 630 / 1250 / 1600 / 2000 / 2500 / 3150* A |
| Power-frequency withstand voltage (1 min) | 42 kV (12 kV) / 65 kV (24 kV) |
| Lightning impulse withstand voltage | 75 kV (12 kV) / 125 kV (24 kV) |
| Rated short-circuit breaking current | 12 kV: 25 / 31.5 / 40 / 50 kA; 24 kV: 25 / 31.5 kA |
| Short-time withstand current (4 s) | 12 kV: 25 / 31.5 / 40 / 50 kA; 24 kV: 25 / 31.5 kA |
| Peak withstand / making current | 12 kV: 63 / 80 / 125 / 135 kA; 24 kV: 63 / 80 kA |
| Rated operating sequence | O-0.3s-CO-180s-CO |
| Single / back-to-back capacitor bank breaking current | 630 / 400 A |
| Mechanical life | 30,000 operations |
| Opening / closing time | 20-50 ms / 30-70 ms |
| Closing / opening and motor voltage | AC 110/220 V, DC 110/220 V; charging time <= 10 s |
| Construction | Withdrawable (W) or fixed (F); spring operating mechanism |
Standards & operating conditions
The SecoVac series is type-tested for temperature rise, dielectric withstand, short-time and peak withstand current, mechanical life and short-circuit switching capability.
| GB / DL standards | GB/T 1984-2014; DL/T 403-2000 |
| IEC / DIN standards | IEC 62271-100:2012; IEC 60694:2002; DIN VDE 0671 |
| IEEE version (15 kV class) | IEEE C37.04, C37.06, C37.09, C37.20.2 |
| Ambient temperature | Max +40 °C; min -15 °C (standard order); max daily average +35 °C |
| Relative humidity at 25 °C | Daily average <= 95%; monthly average <= 90% |
| Altitude | Standard version up to 1000 m; high-altitude version on request |
| Seismic intensity | Not exceeding 8 degrees |
| Site conditions | Indoor; no dripping water, fire/explosion hazard, corrosive gas, severe pollution or violent vibration |
IEEE supplement: SecoVac VB2 Plus IEEE brochure (PDF)
Key features
Vacuum interrupter
One-shot sealing process, high vacuum up to 10^-5 Pa and axial magnetic field interruption for strong arc extinction and long contact life.
Solid-encapsulated pole
The high-voltage circuit is fully encapsulated in solid insulation, reducing environmental influence and providing maintenance-free pollution and salt-spray resistance.
Modular spring mechanism
Modular design with integrated energy-storage shaft, motor/manual clutch, holding latch and cam output for stable operation and easy accessory fitting.
Smart-ready options
Optional temperature monitoring, mechanical-characteristic and secondary-component monitoring, motor-driven trolley control and digital analysis for predictive maintenance.
Need a SecoVac VB2 Plus quote or selection support?
Send us the voltage, rated current, breaking current, installation type and control voltage. We will confirm the configuration and offer.