Moulded case circuit breaker · 630-1600 A · 3P/4P
ComPacT NS630b-1600A
630-1600 A · Ui 1000 V · Icu up to 150 kA · N/H/L
Schneider ComPacT NS630b to NS1600 circuit breakers, 630-1600 A, 3/4 poles, Ui 1000 V, with Icu up to 150 kA. Available in N/H/L breaking types, fixed or withdrawable.
630-1600 A
Rated current
1000 V
Insulation voltage
150 kA
Max breaking capacity
N/H/L
Breaking type
Technical parameters
Data from Schneider ComPacT NS630b-1600A catalog 2025. Values vary by type and voltage; confirm the exact configuration before ordering.
| Type / rated current In @50 °C | NS630b / NS800 / NS1000 / NS1250 / NS1600: 630 / 800 / 1000 / 1250 / 1600 A |
| Poles | 3 / 4 |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Rated operational voltage Ue | AC 50/60 Hz, 690 V |
| Ultimate breaking capacity Icu @380/415 V | 50 / 70 / 150 kA rms (N / H / L type) |
| Ultimate breaking capacity Icu @220/240 V | 85 / 150 kA rms (by type) |
| Service breaking capacity Ics @380/415 V | Up to 150 kA |
| Breaking performance types | N / H / L |
| Connection | Fixed (front / bare cable); withdrawable (rear, on chassis) |
| Control | Manual toggled handle, direct/extended rotary handle, electrical |
| Isolation function | Yes |
| Pollution degree | III |
Standards
| Standards | IEC 60947-2 / EN 60947-2 |
Key features
Protection and measurement
Integrated protection functions including long-delay overload protection Ir; measuring and control functions available.
Isolation
Isolation function compliant with IEC/EN 60947-2 for safe maintenance.
Flexible installation
Fixed and withdrawable versions, front or rear connection, manual or electrical operation.
Need a ComPacT NS630b quote or selection support?
Send us the frame type, rated current, breaking capacity and connection. We will confirm the configuration and offer.
Request a quote