Isolating spark gap · with cable · 100 kA
DEHN EXFS 100 KU Isolating Spark Gap
100 kA (10/350 µs) · Class H · 2 × 2 m cable
DEHN EXFS 100 KU is an isolating spark gap with waterproof sheath and connecting cable for above- or underground installation in hazardous areas.
100 kA
Iimp (10/350 µs)
Class H
Class
IP67
Protection
923 101
Part no.
Technical parameters
Data from DEHN product data sheet 923 101, last update 07/2024.
| Type | Isolating spark gap with connecting cable |
| Part no. | 923 101 |
| Standard | EN 62561-3 / IEC 62561-3 |
| Lightning impulse current (10/350 µs) | 100 kA |
| Lightning current carrying class | Class H |
| Nominal discharge current (8/20 µs) | 100 kA |
| Rated power-frequency withstand voltage | 250 V (50/60 Hz) |
| Rated impulse sparkover voltage | ≤ 1.25 kV |
| Enclosure | 123 mm long · 34 mm dia. · waterproof plastic sheath |
| Connection cable | NYY-J 1×25 mm², 2 × approx. 2000 mm |
| Weight | 1.98 kg |
Standards & operating conditions
| ATEX approval | DEKRA 11ATEX0178 X · II 2 G Ex d IIC T6 Gb / II 2 D Ex tb IIIC T80 °C Db IP 66/67 |
| IECEx approval | IECEx KEM 09.0051X · Ex d IIC T6 Gb / Ex tb IIIC T80 °C Db IP 66/67 |
| Operating temperature | -40 °C to +60 °C; installation -5 °C to +50 °C |
| Degree of protection | IP 67 |
Key features
Pre-fitted connecting cable
Supplied with two approx. 2 m NYY-J 1×25 mm² cables for above- or underground installation.
Adjustable cable length
Waterproof sheath can be shortened for short connecting cables.
Hazardous areas
Approved to ATEX Directive 2014/34/EU and IECEx for gas and dust atmospheres.
Need an EXFS 100 KU quotation or selection support?
Send us the installation conditions and cable length required. We will confirm the configuration and offer.
Request a quote