Isolating spark gap · 100 kA · ATEX / IECEx
DEHN EXFS 100 Isolating Spark Gap
100 kA (10/350 µs) · Class H · IP67
DEHN EXFS 100 is an isolating spark gap for lightning equipotential bonding and indirect earthing of functionally isolated parts, approved for hazardous areas under ATEX and IECEx.
100 kA
Iimp (10/350 µs)
Class H
Class
IP67
Protection
923 100
Part no.
Technical parameters
Data from DEHN product data sheet 923 100, last update 07/2024.
| Type | Isolating spark gap |
| Part no. | 923 100 |
| Standard | EN 62561-3 / IEC 62561-3 |
| Lightning impulse current (10/350 µs) | 100 kA |
| Lightning current carrying class | Class H |
| Nominal discharge current (8/20 µs) | 100 kA |
| Rated power-frequency withstand voltage | 250 V (50/60 Hz) |
| DC withstand voltage | 354 V |
| Rated impulse sparkover voltage | ≤ 1.25 kV |
| Enclosure | 100 mm long · 45.5 mm dia. · plastic sheath |
| Connection | M10 threaded bushing, 2 × M10 × 25 mm with spring washers |
| Weight | 289 g |
Standards & operating conditions
| ATEX approval | DEKRA 11ATEX0178 X · II 2 G Ex db IIC T6 Gb / II 2 D Ex tb IIIC T80 °C Db IP 66/67 |
| IECEx approval | IECEx KEM 09.0051X · Ex db IIC T6 Gb / Ex tb IIIC T80 °C Db IP 66/67 |
| Other approvals | UL, Inmetro (TÜV 17.0698 X) |
| Operating temperature | -20 °C to +60 °C |
| Degree of protection | IP 67 |
Key features
Lightning equipotential bonding
For indirect connection / earthing of functionally isolated parts under lightning conditions, per IEC 62305.
Hazardous areas
Approved to ATEX Directive 2014/34/EU and IECEx for gas and dust atmospheres.
Robust spark gap
Plastic sheath with M10 threaded screws; IP67 for indoor and outdoor use.
Need an EXFS 100 quotation or selection support?
Send us the installation conditions and approval requirements. We will confirm the configuration and offer.
Request a quote