Type 2 SPD · 3+1 circuit · 20/40 kA
DEHN VT2 M TT 385 CN Type 2 SPD
In 20 kA · Imax 40 kA · 385 V · 3+1
Modular Type 2 surge protective device for TT and TN-S systems using a 3+1 circuit, with pre-wired base, plug-in modules and dynamic thermal disconnection.
20 kA
Nominal discharge current
40 kA
Max. discharge current
≤ 1.75 kV
Voltage protection level
3+1
Circuit
Technical parameters
Data from DEHN product data sheet 955 427, edition 03/2025.
| Model | VT2 M TT 385 CN |
| Part no. | 955 427 |
| Standard | GB/T 18802.11 / IEC 61643-11 |
| SPD class | Type 2 / Class II |
| Circuit | 3+1 for TT and TN-S systems |
| Nominal voltage (UN) | 230 / 400 V (50/60 Hz) |
| Max. continuous operating voltage | L-N: 385 V · N-PE: 255 V |
| Nominal discharge current (8/20 µs) | 20 kA |
| Max. discharge current (8/20 µs) | 40 kA |
| Voltage protection level | L-N ≤ 1.75 kV · N-PE ≤ 1.5 kV |
| Response time | L-N ≤ 25 ns · N-PE ≤ 100 ns |
| Max. backup fuse | 125 A gG |
| Short-circuit withstand | 25 kArms |
| TOV withstand | L-N: 335 V / 5 s, 440 V / 120 min; N-PE: 1200 V / 200 ms |
| Connection cross-section | 4 mm² min. solid/flexible · 35 mm² max. stranded / 25 mm² flexible |
| Weight | 506 g |
Standards & operating conditions
| Mounting | 35 mm DIN rail per EN 60715 |
| Size | 4 modules per DIN 43880 |
| Degree of protection | IP 20 |
| Housing | Grey PA6 |
| Location | Indoor |
| Operating temperature | -40 °C to +80 °C |
Key features
Pre-wired unit
Complete unit consisting of base and plug-in protection module.
High discharge capacity
High-performance zinc oxide varistor and gas discharge tube.
Dynamic thermal disconnection
High-reliability SPD monitoring device with green/red status indication.
Need a VT2 M TT 385 CN quotation?
Send us the supply system and installation conditions. We will confirm the configuration and offer.
Request a quote