Home/Products/EasyPact CVS MCCB
EasyPact CVS moulded case circuit breaker
Moulded case circuit breaker · 63-630 A · 3P/4P

EasyPact CVS MCCB

63-630 A · Ui 690 V · Icu up to 100 kA · thermal-magnetic

Schneider EasyPact CVS moulded case circuit breakers, 63-630 A, 3/4 poles, for low-voltage distribution protection. Reliable isolation, Class II insulation, complete accessories and multiple mounting options.

63-630 A
Rated current
690 V
Insulation voltage
100 kA
Max breaking capacity
3P/4P
Poles

Technical parameters

Data from Schneider EasyPact CVS catalog 2025. Icu/Ics vary by frame and breaking type; confirm the exact configuration before ordering.

FramesCVS63 / 100 / 125 / 160 / 250 / 400 / 630
Poles3 / 4
Rated current In @40 °C16 - 630 A (by frame)
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp6 / 8 kV (by frame)
Rated operational voltage UeAC 50/60 Hz, 440/500 V
Ultimate breaking capacity Icu @220/230 VUp to 100 kA rms (B/F/N/HM types)
Ultimate breaking capacity Icu @380/400 VUp to 70 kA rms
Service breaking capacity Ics @220/230 VUp to 75 kA rms
Utilisation categoryA
Isolation functionYes, compliant with IEC 60947-2
Mechanical life (C-O cycles)13,000 - 20,000
Electrical life @415 VUp to 8,000 (In/2), 4,000 (In)
Trip unitThermal-magnetic; VigiPact residual-current relay available
Mounting / connectionFixed front, plug-in and drawout (CVS100)

Standards and environment

StandardsIEC 60947-1 / IEC 60947-2 / GB 14048.1 / GB 14048.2
Pollution degreeIII (industrial, per IEC 60947-1 / 60664-1)
Operating temperature-25 ~ +70 °C (derating above 40 °C; motor protection above 65 °C)
Storage temperature-50 ~ +85 °C
Degree of protectionBare breaker: IP40/IK07 (toggle), IP54/IK08 (extended rotary handle)
EnvironmentRoHS compliant; production sites ISO 14001

Key features

Reliable isolation

All CVS breakers comply with IEC 60947-2 isolation: OFF isolation position, padlock only with contacts open, reliable position indication even with rotary/motor operators.

Class II insulation

All breakers are Class II insulated and can be installed in Class II switchgear without reducing insulation level.

Residual current protection

VigiPact residual-current relays can be combined with CVS breakers for earth leakage protection.

Complete accessories

Auxiliary contacts, shunt trip, undervoltage release, rotary handles, phase barriers and plug-in/drawout bases.

Need a CVS quote or selection support?

Send us the frame current, poles, breaking capacity and mounting type. We will confirm the exact configuration and offer.