EasyPact EZD MCCB
100-630 A · Ui 690 V · Icu up to 100 kA · thermal-magnetic
Schneider EasyPact EZD moulded case circuit breakers, 100-630 A, 3/4 poles, designed for secondary distribution, civil buildings and M&E applications. Complete functions, flexible installation, easy maintenance and excellent value.
Technical parameters
Data from Schneider EasyPact EZD catalog 2025. Icu/Ics vary by frame and type; confirm the exact configuration before ordering.
| Frame / rated current In (40 °C) | EZD100/125/160/250/400/630: 100 / 100 / 125 / 160 / 250 / 400 / 630 A |
| Poles | 3 / 4 |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Rated operational voltage Ue | AC 50/60 Hz, 550 V (100-250), 440 V (400-630) |
| Ultimate short-circuit breaking capacity Icu @380/400 V | Up to 50 kA rms (by type B/F/N/E/M/S) |
| Ultimate breaking capacity Icu @220/230 V | Up to 100 kA rms |
| Service short-circuit breaking capacity Ics | Up to 70 kA @220/230 V; up to 50 kA @380/400 V |
| Utilisation category | A |
| Isolation function | Yes, compliant with IEC 60947-2 |
| Mechanical life (C-O cycles) | 8,500 - 10,000 |
| Electrical life @400 V In | 4,000 - 5,000 |
| Trip unit | Thermal-magnetic (EZD630: electronic) |
| Mounting / connection | Fixed, front connection; plug-in available (160-630) |
Standards and environment
| Standards | IEC 60947-2 / EN 60947-2 / GB 14048.2 |
| Operating temperature | -25 ~ +70 °C (100% performance at 50 °C for 100-250 A, 40 °C for 400-630 A) |
| Storage temperature | -35 ~ +85 °C |
| Damp heat | IEC 60068-2-30: 95% RH at 45 °C; salt mist IEC 60068-2-11 |
Key features
Easy to use
Complete function set, flexible installation and simple maintenance; ideal for secondary distribution, civil building and M&E markets.
Reliable isolation
All EZD breakers are suitable for isolation per IEC 60947-2: contact isolation at OFF, padlock only when all contacts open, reliable position indication.
Wide accessory range
Auxiliary contacts AX/AL, shunt trip SHT, undervoltage release UVR, PM2000 metering with Modbus communication, rotary handles.
Residual current version
VigiEZD residual-current breakers available with adjustable sensitivity 0.03-1 A and adjustable time delay.