EasyPact MVS ACB
400-4000 A · Icu up to 85 kA · Ics=100%Icu · N/N1b/H/T
Schneider EasyPact MVS air circuit breakers, 400-4000 A, 3/4 poles, with Ics = 100% Icu and four breaking types. Equipped with MVS Trip System control units for measurement, protection and communication.
Technical parameters
Data from Schneider EasyPact MVS catalog 2025. Values vary by type and frame; confirm the exact configuration before ordering.
| Type / rated current In @40 °C | MVS06/08/10/12/16/20/25/32/40: 630-4000 A |
| Poles | 3 / 4 |
| Ultimate breaking capacity Icu @220-440 V | 85 kA rms (T type) |
| Service breaking capacity Ics | 100% Icu |
| Short-time withstand current Icw (1 s) | 85 kA rms (T type) |
| Closing capacity Icm @220-440 V | 187 kA peak (T type) |
| Utilisation category | B |
| Breaking time | 25 ms |
| Closing time | < 70 ms |
| Mechanical life (C/O cycles) | 20,000 maintenance / 10,000 non-maintenance |
| Electrical life (C/O cycles, non-maintenance) | 5,000-6,000 |
| Connection | Horizontal / vertical (interchangeable terminals) |
| Breaking types | N / N1b / H / T |
Standards and environment
| Standards | IEC 60947-2 (circuit breaker); IEC 60947-3 (switch-disconnector version) |
| Isolation | Suitable for isolation per IEC 60947-2 |
| Pollution degree | 3 / 4 (per IEC 60664-1, by version) |
| Ambient temperature | 40 °C rated (derating above 40 °C per table) |
Key features
Reliable breaking
Four breaking types N, N1b, H and T for building distribution and industrial applications; Ics = 100% Icu.
Innovative Trip System
MVS Trip System control units provide precise measurement, protection, data storage, event records and signal alarms.
Flexible configuration
Two frame sizes from 400 to 4000 A, interchangeable horizontal/vertical terminals, common accessories and modular design.
Need an MVS quote or selection support?
Send us the rated current, breaking type, poles and control unit. We will confirm the configuration and offer.
Request a quote