Home/Products/GEIS MAST Metal-Clad Switchgear
GEIS MAST metal-clad switchgear 5-15kV
Metal-clad switchgear · 5-15 kV · 1200/2000 A · IEEE C37

GEIS MAST Metal-Clad Switchgear

5-15 kV · 1200/2000 A · 31.5/40 kA · two-high breaker

GEIS MAST is a metal-clad switchgear fully tested to IEEE standards for 5-15 kV, 50/60 Hz, 1200-2000 A and up to 40 kA short-circuit rating. It uses SecoVac embedded-pole vacuum circuit breakers in a two-high, indoor NEMA 1 enclosure.

15 kV
Rated maximum voltage
2000 A
Rated continuous current
40 kA
Short-time withstand
2-high
Breaker stacking

Technical parameters

Data from GEIS MAST Metal-Clad Switchgear Catalogue (IEEE version). Values vary by configuration; confirm the exact breaker and switchgear rating before ordering.

SeriesGEIS MAST Metal-Clad Switchgear
Rated maximum voltage15 kV (5-15 kV applications)
Rated maximum continuous current1200 / 2000 A (switchgear); SecoVac VB2 Plus-15 breaker up to 3000 A
Rated frequency50 / 60 Hz
Power-frequency withstand voltage (1 min)Phase-to-phase / to earth 36 kV; across isolating distance 36 kV (breaker 36/40 kV)
Lightning impulse withstand voltagePhase-to-phase / to earth 95 kV; across isolating distance 95 kV (breaker 95/105 kV)
Rated short-time withstand current31.5 / 40 kA (2 s)
Rated peak withstand current82 / 104 kA
Rated short-circuit breaking current31.5 / 40 kA
EnclosureIndoor NEMA 1; metal-clad, fully compartmentalized with grounded metal barriers
ConstructionTwo-high breaker stacking; withdrawable breakers, VT/CPT and fuse trucks
External dimensions (W x D x H)914 x 2387 x 2413 mm (36 x 94 x 95 inch)
Circuit breakerSecoVac VB2 Plus-15 embedded-pole VCB, GAL spring mechanism, 60,000 mechanical operations tested (design life up to 90,000)

Standards & operating conditions

IEEE standardsIEEE C37.20.2, C37.04, C37.06, C37.09, C37.010, C37.012, C37.11, C37.100.1
Ground and test deviceIEEE Std C37.20.6 (4.76-15 kV grounding and testing devices)
Operating ambient temperatureMaximum +40 °C; minimum -30 °C; daily average <= 35 °C
Storage ambient temperatureMaximum +40 °C; minimum -40 °C; dry place away from direct sunlight and rain
AltitudeMaximum 2000 m (6600 ft)
Relative humidity24-hour average <= 95%; 1-month average <= 90%

Key features

Design for safety

Fully compartmentalized construction with grounded metal barriers between breaker, bus, cable and control compartments; automatic grounded shutters and comprehensive interlocking.

Standard interlocking

Breaker can only move between test and connect positions when open; secondary plug can only be removed at test position; breaker cannot be closed between positions; shutters close automatically on racking out.

Two-high configuration

Two-high breaker stacking gives flexible configuration, reduced floor space and easy expansion; Main-Tie-Main combinations available.

Drawout design

Drawout circuit breakers, VT/CPT and fuse trucks for easy maintenance; lift truck and optional ground-and-test device for safe handling and testing.

Applications

Utilities and power plants, network substations, generator switchgear, oil and gas, mining, pulp and paper, data centres, hospitals, airports and railways.