Hager MCP 6kA Residual Current Circuit Breaker (RCBO)
6 kA · 230 V AC · 1P+N · 10/30 mA Class A · IEC 61009
The Hager MCP series RCBO combines miniature circuit breaker overload and short-circuit protection with residual-current (leakage) protection in one device, with isolation function. It offers 6 kA breaking capacity, 1P+N, rated current 6-40 A, and 10/30 mA Class A electronic residual protection, tripping within 0.1 s.
Technical parameters
Data from Hager official MCP terminal distribution system brochure (CN 2025-09).
| Product family | Hager MCP series 6 kA residual current circuit breaker with overcurrent protection (RCBO) |
| Standards | IEC 61009, GB/T 16917.1-2003 and GB/T 16917.22-2008 |
| Trip type | Electronic ELE, Class A |
| Breaking capacity | 6000 A |
| Rated voltage | 230 V AC |
| Poles | 1P+N |
| Rated current | 6-40 A C curve; 6-25 A D curve |
| Rated residual operating current | 10 mA / 30 mA |
| Rated residual making/breaking capacity | 3000 A (1 module) / 1500 A (2 modules) |
| Operating time | <= 0.1 s at rated residual current |
| Impulse withstand voltage | 4 kV |
| Rated frequency | 50 Hz |
| Mechanical / electrical life | 20000 / 10000 operations |
| Degree of protection | IP20 |
| Model examples | ADP606P, ADP616P, ADP625P, ADP640P |
Standards & operating conditions
| Connection | Hard wire 25 mm2, soft wire 16 mm2, torque 2.8 Nm |
| Ambient temperature | -5 C to +55 C (1 module); -25 C to +40 C (2 modules) |
| Incoming / outgoing | Top in, bottom out |
| Isolation function | Combines MCB overload/short-circuit protection with residual-current protection, with isolation function |
Key features
Integrated protection
Combines miniature circuit breaker overload/short-circuit protection and residual-current protection in one device
Multiple sensitivities
Available with 10 mA and 30 mA residual operating currents for different protection needs
Fast tripping
Trips within 0.1 s at rated residual current for enhanced personal safety
Compact design
1P+N width approx. 17.8 mm per module for space-saving distribution boards
Need an MCP RCBO?
Send us the rated current, residual sensitivity and tripping curve. We will confirm the configuration and offer.
Request a quote