Home/Products/Schneider I-LINE W Busway System
Schneider Electric I-LINE W medium and high current busway system
Copper busway · 400-5000 A · 1000 V · up to IP66

Schneider I-LINE W Busway System

400-5000 A · 1000 V · IP54/65/66 · Icw up to 100 kA

Schneider Electric I-LINE W is a copper busway system for medium and high current distribution from 400 A to 5000 A. It uses a sandwich conductor arrangement, silver-plated copper conductors and a fully enclosed housing, with CCC certification and optional smart temperature monitoring.

400-5000 A
Rated current
1000 V
Rated voltage
100 kA
Max short-time withstand
IP66
Max protection

Technical parameters

Data from Schneider I-LINE W catalog SCDOC1897 (2024). Icw and Ipk values depend on the current rating; confirm the exact configuration before ordering.

SeriesSchneider Electric I-LINE W
Rated current400 / 630 / 800 / 1000 / 1250 / 1600 / 2000 / 2500 / 3200 / 4000 / 5000 A
Rated operational voltage1000 V
Rated insulation voltage1000 V
Frequency50 Hz
Enclosure protection degreeIP54 / IP65 / IP66
Rated short-time withstand current Icw (3C report)20 kA (400 A) / 30 kA (630-800 A) / 50 kA (1000-1250 A) / 80 kA (1600-3200 A) / 100 kA (4000-5000 A)
Rated peak short-circuit current Ipk (3C report)40 kA (400 A) / 63 kA (630-800 A) / 105 kA (1000-1250 A) / 176 kA (1600-3200 A) / 220 kA (4000-5000 A)
ConductorHigh-purity electrolytic copper, silver-plated contact surfaces
Conductor resistance R200.205 mΩ/m (400 A) to 0.012 mΩ/m (5000 A), by rating
Voltage drop (40 °C, full load, cosφ=1)0.176 V/m (400 A) to 0.132 V/m (5000 A)
Temperature derating factor1.0 at 40 °C; 0.93 at 45 °C; 0.87 at 50 °C; 0.82 at 55 °C; 0.78 at 60 °C; 0.74 at 65 °C; 0.71 at 70 °C

Standards & certification

Product certificationCCC certification for the full I-LINE W range
StandardsGB/T 7251.1 and GB/T 7251.6
Insulation materialPolyester film, class B 130 °C; >=5000 h test per GB/T 11026.1; halogen-free, UL94 flame retardant
Plug-in unit16-800 A; built-in Schneider breaker, breaking capacity up to 70 kA, Ics=100% Icu, mechanical life 50,000 operations, IP54

Key features

Sandwich construction

Conductors are closely arranged for overall heat dissipation, giving lower temperature rise and a compact footprint.

Fully enclosed housing

Improves protection, reduces dust accumulation, eliminates direct contact with live parts and offers good corrosion resistance.

Fire safety

Internal smoke barriers prevent smoke spreading through the busway; all parts are halogen-free, with no smoke or toxic gas in fire.

Smart temperature monitoring

Zigbee-based monitoring can track more than 1,000 temperature points on one busway run and integrate with EcoStructure.

Applications

Transformer-to-switchgear connections, horizontal workshop distribution and vertical riser supply in high-rise buildings.

Need an I-LINE W busway quote or selection support?

Send us the current rating, voltage, protection degree, route layout and tap-off requirements. We will confirm the configuration and offer.

Request a quote