Vacuum circuit breaker · 12-40.5 kV · up to 6300 A
Siemens 3AE8 VCB
12/24/40.5 kV · up to 6300 A · up to 40 kA · GB 1984
Siemens 3AE8 vacuum circuit breakers, 12/24/40.5 kV, rated current up to 6300 A, breaking current up to 40 kA, compliant with GB 1984 and IEC 62271-100.
12-40.5 kV
Rated voltage
6300 A
Max rated current
40 kA
Max breaking current
4 s
Short-circuit duration
Technical parameters
Data from Siemens 3AE8 catalog 2025. Values vary by voltage and version; confirm the exact configuration before ordering.
| Rated voltage | 12 / 24 / 40.5 kV |
| Rated frequency | 50 Hz |
| Rated 1 min power-frequency withstand voltage (phase-to-earth / open contacts) | 42/48 kV (12 kV), 65/79 kV (24 kV), 95 kV (40.5 kV) |
| Lightning impulse withstand voltage (peak) | 75/85 kV (12 kV), 125/145 kV (24 kV), 185 kV (40.5 kV) |
| Rated current | Up to 6300 A (by voltage and version) |
| Rated short-circuit breaking current | 25/31.5/40 kA (12 kV); 25/31.5 kA (24/40.5 kV) |
| DC component | 52% / 55% |
| Rated short-time withstand current | 25/31.5/40 kA |
| Rated short-circuit duration | 4 s |
| Rated short-circuit making current (peak) | 63/80/110 kA |
| Opening time | ≤ 30 ms |
| Closing time | ≤ 60 ms |
| Arcing time | ≤ 15 ms |
| Power-frequency withstand voltage of secondary circuit (1 min) | 2000 V |
Standards and environment
| Standards | GB 1984 / IEC 62271-100 |
| Ambient air temperature | -5 ~ +40 °C (for -25 °C requirement, contact Siemens) |
| Relative humidity | Up to 95% (daily average) / 90% (monthly average) |
| Installation altitude | Up to 1000 m (higher altitude: contact Siemens) |
| Seismic intensity | Up to 8 degrees |
Key features
Wide voltage range
3AE8 vacuum circuit breakers available at 12 kV, 24 kV and 40.5 kV for medium-voltage applications.
Vacuum interrupter
Sealed vacuum interrupters provide reliable current interruption with short arcing time (≤ 15 ms).
Fast operation
Opening time ≤ 30 ms and closing time ≤ 60 ms for fast switching and system protection.