Home/Products/Siemens SENTRON 5SY Miniature Circuit Breaker
Siemens SENTRON 5SY miniature circuit breaker
SENTRON · Miniature circuit breaker · 0.3-80 A

Siemens SENTRON 5SY Miniature Circuit Breaker

6 / 10 / 15 kA · 1-4P, 1+N, 3+N · A/B/C/D curves

SENTRON 5SY miniature circuit breakers provide short-circuit and overload protection for industrial and mechanical engineering applications. They comply with IEC/EN 60898-1 and are also approved to EN 60947-2 and UL 1077, with rated currents from 0.3 to 80 A and switching capacities of 6, 10 and 15 kA.

0.3-80 A
Rated current
6/10/15 kA
Breaking capacity
A/B/C/D
Trip characteristics
1-4P
Pole versions

Technical parameters

Data from the official Siemens SENTRON 5SY brochure SIEP-B10408-00-7600 and siemens.com/mcb, retrieved 2026-11-21. Ratings vary by order code; confirm the exact MLFB before ordering.

Product familySENTRON 5SY miniature circuit breakers
Pole versions1-, 2-, 3-, 4-pole as well as 1+N and 3+N
Rated current0.3 to 80 A
Rated switching capacity6 / 10 / 15 kA (version dependent)
Tripping characteristicsA (5SY4 / 5SY6), B (residential), C (high inrush currents), D (pulse-generating equipment)
Product standardIEC/EN 60898-1; additionally approved to EN 60947-2 and UL 1077
TerminalsIdentical terminals allow infeed from top or bottom; double terminal chambers for two wires of different cross-sections
MountingCompact DIN-approved device; tool-free snapping onto a standard mounting rail

Standards & operating conditions

Standards and approvalsIEC/EN 60898-1; EN 60947-2 and UL 1077 approvals
Market approvals5SY4 / 5SY6 / 5SY7 approved for Germany, Italy, Russia, USA, Canada and China under IEC/EN 60898-1; 5SY8 for Russia, USA and Canada
Railway versions5SY4, 5SY5 and 5SY7 meet vibration and shock requirements of DIN EN 61373 and DIN EN 50155 category 1B
ApplicationsIndustrial control cabinets, HVAC, EV charging stations, wind turbine auxiliary circuits, PV components, construction site distribution boards; residential via characteristic B

Key features

Short-circuit and overload protection

Protects cables and lines from overload and short circuit; offers backup protection for switching devices and semiconductors

Flexible installation

Identical terminals permit top or bottom infeed; double terminal chambers accept two different wire cross-sections; tool-free DIN-rail mounting

Status indication

Auxiliary switch or fault signal contact allows status to be judged locally or remotely

System expandability

Standardized Siemens accessories and combination with the 5SM6 arc-fault detection unit extend circuit protection functions

Need SENTRON 5SY selection support?

Send us the MLFB, poles, trip characteristic, rated current and quantity. We will confirm the configuration and offer.