Siemens 8DJH 36 Gas-Insulated MV Switchgear
Ur 36 kV · 630 A · Ik up to 25 kA · IEC 62271-103
Siemens 8DJH 36 gas-insulated switchgear for secondary distribution systems up to 36 kV, used in public and industrial energy systems. Rated normal current 630 A, short-time withstand current up to 25 kA.
Technical parameters
Data from Siemens 8DJH 36 catalog HA 40.3 (2022). Values vary by configuration; confirm the exact version before ordering.
| Rated voltage Ur | 36 kV |
| Power-frequency withstand voltage Ud (phase-to-phase / earth / open gap) | 70 kV |
| Withstand voltage across isolating distance | 80 kV |
| Lightning impulse withstand voltage Up (phase-to-phase / earth / open gap) | 170 kV |
| Impulse withstand across isolating distance | 195 kV |
| Rated frequency fr | 50 / 60 Hz |
| Rated normal current Ir (ring-main / breaker / busbar feeders) | 630 A |
| Rated short-time withstand current Ik (tk = 3 s) | up to 20 / 25 kA |
| Rated peak withstand current Ip | up to 63 kA (50 Hz) / 65 kA (60 Hz) |
| Rated short-circuit making current Ima | up to 63 kA (ring-main / breaker feeders) |
| Rated filling pressure (absolute, at 20 °C) | 150 kPa; minimum functional 130 kPa |
| Ambient air temperature (operation) | -25 to +55 °C |
Standards & endurance
| Switch-disconnector standard | IEC 62271-103 |
| Mechanical endurance | Class M1 (1000 operating cycles) |
| Electrical endurance | Class E3 (100 operating cycles with Iload) |
| Capacitive switching | Class C2 (no restrikes) |
| Management system | ISO 9001, ISO 14001, BS OHSAS 18001 certified manufacturing |
Key features
Gas-insulated design
8DJH 36 is a gas-insulated medium-voltage switchgear for secondary distribution systems up to 36 kV.
Typical applications
Used in public and industrial energy systems for reliable secondary distribution.
Three-position switch-disconnector
Three-position switch-disconnector compliant with IEC 62271-103, with M1 mechanical and E3 electrical endurance.
Need an 8DJH 36 quote or selection support?
Send us the feeder configuration, rated current and installation requirements. We will confirm the version and offer.
Request a quote