Eco-friendly RMU · 7.2-24 kV · clean air insulation
SM AirSeT Ring Main Unit
7.2/12/17.5/24 kV · clean air · 25 kA/1 s
Schneider SM AirSeT sustainable ring main unit, 7.2/12/17.5/24 kV, using clean air (no SF6) for insulation, with rated short-time withstand current 25 kA/1 s and continuous current up to 1250 A.
7.2-24 kV
Rated voltage
25 kA
Short-time withstand
1250 A
Max current
SF6-free
Insulation gas
Technical parameters
Data from Schneider SM AirSeT catalog. Values vary by configuration; confirm the exact version before ordering.
| Rated voltage Ur | 7.2 / 12 / 17.5 / 24 kV |
| Rated frequency fr | 50/60 Hz |
| Rated short-duration power-frequency withstand voltage (1 min) | 20 / 28 / 38 / 50 kV |
| Rated lightning impulse withstand voltage | 60 / 75 / 95 / 125 kV |
| Rated continuous current | Switch 400/630 A, disconnector 1250 A |
| Rated short-time withstand current | 25 kA/1 s; 20 kA/3 s |
| Rated peak withstand current | 62.5 kA |
| Capacitive switching class | C2 |
Standards and environment
| Standards | Per Schneider SM AirSeT catalog (IEC 62271 series) |
Key features
SF6-free insulation
Uses clean air for insulation, eliminating SF6 greenhouse gas.
Flexible configurations
Switch, disconnector, earthing switch and motorized mechanisms in one range.
Long mechanical life
Switch mechanical endurance up to 10,000 operations (M2).