3P+N/4P Smart MCB
6~125 A · AC 400 V · RS485 · multi-protection
A smart miniature circuit breaker for IoT energy monitoring, electrical safety and intelligent control. It measures and analyses power consumption in real time and protects against overload, short circuit, overvoltage, undervoltage, phase loss and overtemperature. Built-in power supply, compact design and 35 mm DIN-rail mounting.
Technical parameters
From the manufacturer's user manual. Confirm the exact configuration before ordering.
| Poles / occupied size | 3P+N / 4P (72 mm) |
| Rated current setting range | 6~125 A |
| Rated operational voltage Ue | AC 400 V |
| Rated frequency | 50 Hz |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Rated ultimate short-circuit breaking capacity Icn | 6 kA |
| Rated service short-circuit breaking capacity Ics | 6 kA |
| Mechanical / electrical life | 10,000 / 6,000 operations |
| Instantaneous trip characteristic | Type C |
| Operating power consumption | 0.3 W |
| Degree of protection | IP20 |
| Mounting | Standard 35 mm DIN rail |
| Connection capacity | up to 50 mm² |
Protection functions
Thresholds shown are factory defaults; ranges are adjustable as stated in the manual.
Overload protection
Trip when current exceeds the overload threshold (factory 120% In, adjustable 115%~140% In); alarm threshold factory 113% In (90%~125% In).
Instantaneous protection
5 In: no trip within 100 ms. 10 In: trips in less than 100 ms.
Overvoltage protection
Trip/alarm when phase voltage exceeds the threshold for the set time. Factory trip 275 V (250~300 V), alarm 260 V (240~300 V), delay 6000 ms (3000~9000 ms).
Undervoltage protection
Factory trip 160 V (50~180 V), alarm 180 V (100~190 V), delay 3000 ms (600~5000 ms).
Phase-loss protection
Trip/alarm when any phase voltage falls below 132 V for 4000 ms.
Overtemperature protection
Trip/alarm when busbar temperature exceeds the threshold. Factory trip 85 °C (30~100 °C), alarm 75 °C (30~75 °C), delay 30 s (6~60 s).
Event logging
Records the latest 10 trip events, 10 position-change events, 10 alarm events, 10 temperature-alarm events and 10 function on/off events, with cause, phase, time, current and voltage.
Remote control
In remote mode, opening/closing commands can be sent over the communication channel; interval between remote commands must exceed 5 s. Local mode is handle operation only.
Measurement & communication
Metering resolution and accuracy within rated ranges; RS485 communication for telemetry and control.
| Resolution | 0.1 V / 1 mA / 0.1 W / 0.01 kWh / 0.01 Hz / 0.1% / 0.1 °C |
| Accuracy | ±1% (voltage, current, power, energy, frequency, PF); ±5 °C (temperature) |
| Interface | RS485 |
| Frame | 8 data bits, 1 stop bit, even parity |
| Default baud rate | 9600 bps |
| Supported baud rates | 1200 / 2400 / 4800 / 9600 / 19200 / 115200 bps |
| Purpose | Telemetry to platform; parameter setting and remote commands; internal debugging |
Overload & instantaneous tripping
Inverse-time curve t=(2In)²·Tn/I² per the manual.
| Circuit current | Action type | Action time |
|---|---|---|
| 1.13 In | No trip | ≥ 2 h no trip |
| 1.45 In | Inverse time | 2~50 min |
| 2 In | Inverse time | 3~30 s |
| 2.55 In | Inverse time | 3~25 s |
| ≥ 3 In | Definite time | 0.3~3 s |
| Instantaneous current | Action |
|---|---|
| 5 In | No trip within 100 ms |
| 10 In | Trips in less than 100 ms |
Voltage & temperature trip thresholds
Factory values with adjustable ranges in brackets. Auto-reclose applies in remote mode only.
| Protection | Trip threshold (factory / range) | Alarm threshold (factory / range) | Trigger delay (factory / range) |
|---|---|---|---|
| Overvoltage | 275 V (250~300 V) | 260 V (240~300 V) | 6000 ms (3000~9000 ms) |
| Undervoltage | 160 V (50~180 V) | 180 V (100~190 V) | 3000 ms (600~5000 ms) |
| Phase loss | 132 V | 132 V | 4000 ms |
| Overtemperature | 85 °C (30~100 °C) | 75 °C (30~75 °C) | 30 s (6~60 s) |
Smart functions & indicators
Remote upgrade
Supports remote firmware upgrade with breakpoint resume; upgrade files carry hardware-version and validity checks.
Auto reclosing
In remote mode, auto recloses within 1 minute after voltage or temperature faults clear. User can enable or disable.
Real-time clock
Built-in high-accuracy RTC provides time stamps for switching, alarms and energy statistics.
Scheduled switching
Up to 5 configurable daily open/close schedules in 24-hour format; remote mode only.
Load profile
Records up to 254 frozen points (time, energy, voltage, current, active power) at 15/30/60 min intervals; default 30 min.
| Indicator | Status |
|---|---|
| System power-on | All indicators flash quickly |
| Run lamp | Green steady = open; red steady = closed |
| Remote/local lamp | Red off = remote; red steady = local |
| Overcurrent lamp | Red flashing = trip; red steady = alarm |
| Over/undervoltage lamp | Red flashing = trip; red steady = alarm |
Dimensions & wiring
Dimensional drawing and connection diagram from the manual (3P shown).


Operating & storage environment
| Installation site | Free of conductive dust, corrosive or explosive gas, and rain or snow |
| Altitude | ≤ 2000 m |
| Operating temperature | -25 °C ~ +60 °C; 24 h average ≤ +50 °C |
| Relative humidity | ≤ 50% at +40 °C; higher at lower temperatures |
| Storage conditions | -10 ~ +45 °C; ≤ 90% RH at +20 °C; dry and ventilated |