Home/Products/3P+N/4P Smart MCB
3P+N/4P smart MCB dimensional drawing
Smart MCB · 3P+N/4P · IoT energy monitoring

3P+N/4P Smart MCB

6~125 A · AC 400 V · RS485 · multi-protection

A smart miniature circuit breaker for IoT energy monitoring, electrical safety and intelligent control. It measures and analyses power consumption in real time and protects against overload, short circuit, overvoltage, undervoltage, phase loss and overtemperature. Built-in power supply, compact design and 35 mm DIN-rail mounting.

6~125 A
Rated current
AC 400 V
Rated voltage
6 kA
Breaking capacity
RS485
Communication

Technical parameters

From the manufacturer's user manual. Confirm the exact configuration before ordering.

Poles / occupied size3P+N / 4P (72 mm)
Rated current setting range6~125 A
Rated operational voltage UeAC 400 V
Rated frequency50 Hz
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4 kV
Rated ultimate short-circuit breaking capacity Icn6 kA
Rated service short-circuit breaking capacity Ics6 kA
Mechanical / electrical life10,000 / 6,000 operations
Instantaneous trip characteristicType C
Operating power consumption0.3 W
Degree of protectionIP20
MountingStandard 35 mm DIN rail
Connection capacityup to 50 mm²

Protection functions

Thresholds shown are factory defaults; ranges are adjustable as stated in the manual.

Overload protection

Trip when current exceeds the overload threshold (factory 120% In, adjustable 115%~140% In); alarm threshold factory 113% In (90%~125% In).

Instantaneous protection

5 In: no trip within 100 ms. 10 In: trips in less than 100 ms.

Overvoltage protection

Trip/alarm when phase voltage exceeds the threshold for the set time. Factory trip 275 V (250~300 V), alarm 260 V (240~300 V), delay 6000 ms (3000~9000 ms).

Undervoltage protection

Factory trip 160 V (50~180 V), alarm 180 V (100~190 V), delay 3000 ms (600~5000 ms).

Phase-loss protection

Trip/alarm when any phase voltage falls below 132 V for 4000 ms.

Overtemperature protection

Trip/alarm when busbar temperature exceeds the threshold. Factory trip 85 °C (30~100 °C), alarm 75 °C (30~75 °C), delay 30 s (6~60 s).

Event logging

Records the latest 10 trip events, 10 position-change events, 10 alarm events, 10 temperature-alarm events and 10 function on/off events, with cause, phase, time, current and voltage.

Remote control

In remote mode, opening/closing commands can be sent over the communication channel; interval between remote commands must exceed 5 s. Local mode is handle operation only.

Measurement & communication

Metering resolution and accuracy within rated ranges; RS485 communication for telemetry and control.

Resolution0.1 V / 1 mA / 0.1 W / 0.01 kWh / 0.01 Hz / 0.1% / 0.1 °C
Accuracy±1% (voltage, current, power, energy, frequency, PF); ±5 °C (temperature)
InterfaceRS485
Frame8 data bits, 1 stop bit, even parity
Default baud rate9600 bps
Supported baud rates1200 / 2400 / 4800 / 9600 / 19200 / 115200 bps
PurposeTelemetry to platform; parameter setting and remote commands; internal debugging

Overload & instantaneous tripping

Inverse-time curve t=(2In)²·Tn/I² per the manual.

Circuit currentAction typeAction time
1.13 InNo trip≥ 2 h no trip
1.45 InInverse time2~50 min
2 InInverse time3~30 s
2.55 InInverse time3~25 s
≥ 3 InDefinite time0.3~3 s
Instantaneous currentAction
5 InNo trip within 100 ms
10 InTrips in less than 100 ms

Voltage & temperature trip thresholds

Factory values with adjustable ranges in brackets. Auto-reclose applies in remote mode only.

ProtectionTrip threshold (factory / range)Alarm threshold (factory / range)Trigger delay (factory / range)
Overvoltage275 V (250~300 V)260 V (240~300 V)6000 ms (3000~9000 ms)
Undervoltage160 V (50~180 V)180 V (100~190 V)3000 ms (600~5000 ms)
Phase loss132 V132 V4000 ms
Overtemperature85 °C (30~100 °C)75 °C (30~75 °C)30 s (6~60 s)

Smart functions & indicators

Remote upgrade

Supports remote firmware upgrade with breakpoint resume; upgrade files carry hardware-version and validity checks.

Auto reclosing

In remote mode, auto recloses within 1 minute after voltage or temperature faults clear. User can enable or disable.

Real-time clock

Built-in high-accuracy RTC provides time stamps for switching, alarms and energy statistics.

Scheduled switching

Up to 5 configurable daily open/close schedules in 24-hour format; remote mode only.

Load profile

Records up to 254 frozen points (time, energy, voltage, current, active power) at 15/30/60 min intervals; default 30 min.

IndicatorStatus
System power-onAll indicators flash quickly
Run lampGreen steady = open; red steady = closed
Remote/local lampRed off = remote; red steady = local
Overcurrent lampRed flashing = trip; red steady = alarm
Over/undervoltage lampRed flashing = trip; red steady = alarm

Dimensions & wiring

Dimensional drawing and connection diagram from the manual (3P shown).

Dimensions
Wiring diagram

Operating & storage environment

Installation siteFree of conductive dust, corrosive or explosive gas, and rain or snow
Altitude≤ 2000 m
Operating temperature-25 °C ~ +60 °C; 24 h average ≤ +50 °C
Relative humidity≤ 50% at +40 °C; higher at lower temperatures
Storage conditions-10 ~ +45 °C; ≤ 90% RH at +20 °C; dry and ventilated

Need a quote or technical support?

Tell us the pole configuration, rated current and communication requirement — our team will confirm availability and offer a competitive price.

Request a quote