WATSG Automatic Transfer Switch
32-800 A · AC 230/400 V · Ui 1000 V · Modbus
Schneider WATSG automatic transfer switching equipment, 32-800 A, PC class, with patent cylindrical moving contacts, 100 ms short-time withstand, double-break isolation and padlock, full-series Modbus communication, and A/H type controllers for flexible control and monitoring.
Technical parameters
Data from Schneider WATSG catalog 2024. Values are listed by frame size 100/160/250/800. Confirm the exact configuration before ordering.
| Frame sizes | 100 / 160 / 250 / 800 A |
| Rated operational current Ie (AC-33B) | 32/63 · 100 · 125/160/200 · 250/320/400/500 A |
| Rated operational current Ie (AC-33iB) | 32/63/100 · 125/160 · 250 · 320/400/500/630/800 A |
| Poles | 2 / 3 / 4 (800 frame: 3 / 4) |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8000 V |
| Rated operational voltage Ue | AC 50/60 Hz, 230/400 V (800 frame: 400 V) |
| Rated short-circuit making capacity Icm | 7.65 / 17 / 17 / 34 kA |
| Rated short-time withstand current Icw (100 ms) | 5 / 10 / 10 / 17 kA |
| Rated limited short-circuit current Iq (fuse protected) | 80 kA (2P) / 100 kA (3P, 4P); 800 frame: 100 kA |
| Mechanical life | 10,000 operations |
| Electrical life | 6,000 operations |
| Minimum contact transfer time | < 1 s (100/160) · < 1.5 s (250/800) |
| Utilisation category | AC-33B / AC-33iB |
| Equipment class | PC class |
Standards and compliance
| General rules | GB 14048.1 / IEC 60947-1 |
| Transfer switching equipment | GB/T 14048.11 / IEC 60947-6-1 |
| Certification | CCC, RoHS 2.0 |
| Pollution degree | III |
| EMC immunity | ESD / RF radiated / EFT / surge / RF conducted: Level 3; radiation class B |
Operating conditions
| Ambient temperature | -25 ~ +70 °C |
| Storage temperature | -35 ~ +85 °C |
| Altitude | ≤ 2000 m |
| Relative humidity | ≤ 95% at +55 °C |
Key features
Patent cylindrical moving contacts
Reduces friction during contact, accelerates opening/closing and makes transfer smoother and faster.
100 ms short-time withstand
Better than the national standard requirement, improving coordination with line protection.
Modbus communication
Full series supports Modbus, enabling remote signalling, telemetry and remote adjustment; can connect to local and cloud device management systems.
Three control types
Automatic, manual and remote control types to meet different control needs; position feedback is standard.
Double-break isolation and padlock
Standard double-break padlock function for safer operation and maintenance; padlock possible only in OFF position.
A-type / H-type controllers
A-type controller supports multiple plug-in expansion modules; H-type has LCD display and manual/auto keys. T-Helper maintenance assistant available.
Optional over/undervoltage protection
Adjustable thresholds: undervoltage 160-190 V (2P/4P) or 280-360 V (3P); overvoltage 240-280 V (2P/4P) or 420-480 V (3P).
Adjustable transfer / return delay
DIP switches set transfer and return delay: 0 / 5 / 15 / 30 s; working modes include auto-auto recovery, mutual standby and auto-non-recovery.
Indicator status
| Indicator | Function | Status indication |
|---|---|---|
| UI lamp | Power I status | Steady: normal · Flashing: fault |
| UII lamp | Power II status | Steady: normal · Flashing: fault |
| Ion lamp | Power I closed | Steady: closed · Off: open |
| IIon lamp | Power II closed | Steady: closed · Off: open |
| RUN lamp | Operating status | Steady: auto · Off: manual · Flashing: fault alarm |
Optional accessories
| Connection cable | H-type controller standard 2.0 m secondary cable; 3.0 / 4.0 / 5.0 m available on request. |
| Operating handle | One manual operating handle supplied as standard. |